Model | PM11-HF03RTE-100S | ||||||
Capacity | 3000VA/2700W | ||||||
Input | |||||||
Voltage Range | 220 VAC ± 25% | ||||||
Frequency Range | 50HZ ± 10% | ||||||
Output | |||||||
Voltage Range | 220 VAC ± 25% | ||||||
Frequency Range | 50HZ ± 10% | ||||||
Waveform | Sine Wave | ||||||
Output Battery | Battery Size | 8 x 12V100Ah | |||||
Recharge Time | 90% Capacity after 8 hours | ||||||
Backup Time @ % Load || Max Load: 12 Amps | |||||||
|
|||||||
General | |||||||
Tower Size | 440mm x 480mm x 86mm | ||||||
Rackmount Size | 480mm x 440mm x 86mm | ||||||
Weight | 10 kgs | ||||||
Software | USB Management Software | ||||||
SNMP | SNMP card optional extra | ||||||
Battery Box | |||||||
Size | 470mm x 780mm x 615mm | ||||||
Weight | 250 kgs | ||||||
Warranty | |||||||
Unit | Units carry a 24 month warranty and are sold subject to PowerMan standard terms and conditions, a copy of which is available on request. | ||||||
Batteries | The batteries carry a 6 month warranty and are sold subject to PowerMan standard terms and conditions, a copy of which is available on request. |
![]() | High Frequency, transformerless design results in a small compact unit to suit an office or server room environment | |
![]() | On-Line double conversion technology | |
![]() | True sine wave output with less than 3% THD | |
![]() | Zero transfer time | |
![]() | Advanced battery management (ABM) | |
![]() | Batteries automatically charge when inverter is off | |
![]() | UPS will start without mains present (cold start) | |
![]() | Self diagnosis on UPS start up | |
![]() | Lightning and surge protection built in | |
![]() | USB Management Software (SNMP Optional) | |
![]() | LCD Display | |
![]() | Compatible with most brands of generator |